Dimension of Kinco K6 PLC | |||
Parameter | K606EA-30DT | K606EA-30AT | |
I/O and communication port | |||
Digital IO | 14*DI/10*DO(DC24V) | ||
Analog IO | 4*AI/2*AO | ||
Power | DC 24V | AC 220V | |
Connect expansion BD board | 2 | 2 | |
Connect expansion module | 14(Can support K5 series expansion modules) | ||
Communication port | Serial port | Body:2*RS485; BD board:1*RS232 + 1*RS485 | |
CAN | Body:none; BD board:1*CAN | ||
Ehternet | Body:1*Ethernet | ||
High-speed counter | 4 | ||
single-phase | HSC0 and HSC1:Up to 200KHz;HSC2 and HSC3:Up to 6KHz | ||
double-phase | HSC0 and HSC1:Up to 200KHz;HSC2 and HSC3:Up to 2KHz | ||
High-speed output | 4(The output type is relay does not support high-speed output function) | ||
PTO0--PTO2:Up to 200KHz | |||
PTO3:Up to 10KHz(Each channel requires load resistance not exceed 1.5KΩ, | |||
otherwise the maximum output frequency will not be reached) | |||
Edge interrupt | 4, I0.0-I0.3 can be on/off interrupt. | ||
Size | 186*114*76 MM | ||
Memory area | |||
User programme | Maximum. 8K instructions supported | ||
User data memory | M area 4K bytes; V area 16K bytes | ||
Timer | 256 | ||
1ms time base:4 | |||
10ms time base:16 | |||
100ms time base:236 | |||
Counter | 256 | ||
Data back up memory | EEPROM,Maximum. 1K bytes supported. | ||
Retentive memory range | V area (16K bytes) + C area(Counter, 512 bytes) Lithium battery, 3 year lifetime at room temperature | ||
Others | |||
Interrupt | 2, 0.1ms time base. | ||
Realtime Clock | built-in, time deviation is less than 5min/month at 25ºC. | ||
DC24V output power | 300mA,Short circuit protection. |
CPU | Model | Specification |
CPU606 |
K606-24DT
|
DC24V,DI 14*DC24V,DO 10*DC24V
Communication port:2*RS485,1*Ethernet 1 expansion BD board can be connected 14 expansion modules can be connected |
K606-24DR
|
DC24V,DI 14*DC24V,DO 10*Relay
Communication port:2*RS485,1*Ethernet 1 expansion BD board can be connected 14 expansion modules can be connected |
|
K606-24AT
|
AC100-240V,DI 14*DC24V,DO 10*DC24V
Communication port:2*RS485,1*Ethernet 1 expansion BD board can be connected 14 expansion modules can be connected |
|
K606-24AR
|
AC100-240V,DI 14*DC24V,DO 10*Relay
Communication port:2*RS485,1*Ethernet 1 expansion BD board can be connected 14 expansion modules can be connected |
|
CPU608 |
K608-40DT
|
DC24V,DI 24*DC24V,DO 16*DC24V
Communication port:2*RS485,1*Ethernet
2 expansion BD board can be connected
14 expansion modules can be connected
|
K608-40DR
|
DC24V,DI 24*DC24V,DO 16*Relay
Communication port:2*RS485,1*Ethernet 2expansion BD board can be connected 14 expansion modules can be connected |
|
CPU606EA | K606EA-30DT |
DC24V,DI 14*DC24V,DO 10*DC24V 4*IV 2*IV
Communication port:2*RS485,1*Ethernet
2 expansion BD board can be connected
14 expansion modules can be connected
|
K606EA-30AT |
AC100-240V,DI 14*DC24V,DO 10*DC24V 4*IV 2*IV
Communication port:2*RS485,1*Ethernet
1 expansion BD board can be connected
14 expansion modules can be connected
|