| Model | EX2K | EX3K | EX2KL | EX3KL | |
| Capacity | VA/W | 2000VA/1600W | 3000VA/2400W | 2000VA/1600W | 3000VA/2400W |
| Input | Nominal Voltage | 110/115/120VAC or 200/220/230/240VAC | |||
| Voltage Range | 60~138VAC or 115~300VAC | ||||
| Frequency Range | 50Hz : 46~54Hz : 60Hz; 56~64Hz | ||||
| Phase | Single phase with Ground | ||||
| Power Factor | ≥0.97 | ||||
| Output | Voltage | 110/115/120 (1±2%) VAC or 208/220/230/240 (1±2%) VAC | |||
| Frequency | 50/60Hz (Adjustable); 50Hz AC Mode: Follow AC, Battery Mode: 50Hz (1±0.2%) 60Hz AC Mode: Follow AC, Battery Mode: 60Hz (1±0.2%) | ||||
| Wave Form | Pure sine wave | ||||
| Power Factor | 0.8 | ||||
| Harmonic Distortion | ≤3% THD (Linear load); ≤7% THD (Non-linear load) | ||||
| Overload Capacity | 110% ~150% maintain 30s then turn to bypass output, over 150% maintain 200ms | ||||
| Current Crest Ratio | 3 ∶1 | ||||
| Connections | IEC320*6 | IEC320*3 & Terminal block | IEC320*6 | IEC320*3 & Terminal block | |
| Efficiency | TO Battery Mode | 83% | |||
| TO AC Mode | 85% | ||||
| Battery | Type | Sealed free maintenance lead acid battery | |||
| Nominal DC voltage | Built in batteries 12V7.0AH | 96Vdc | 96Vdc | ||
| Quantity | 8 PCS | 8 PCS | Depend on requested back-up time | ||
| Back-up Time (Full Load) | ≥ 7min | ≥ 6min | Depends on the capacity of external battery bank | ||
| Recharge Time | 5 hours to 90% of capacity full discharge | Depends on the capacity of external battery bank | |||
| Charge Current (MAX) | 1.0 A | 1.0 A | 5.0A/ 7.0A | 5.0A/ 8.0A | |
| Charge Voltage (VDC) | 110V±0.6V | 110V±0.6V | 110V±0.6V | 110V±0.6V | |
| Bypass | Automatic Transfer | On overload and UPS failure | |||
| Before UPS Power-on | Default "ON" user adjustable to "YES" | ||||
| Transfer Time | 0ms; less than 4ms from inverter to bypass and vice versa | ||||
| Indicators | LCD Display | UPS status, Battery capacity, loading, Fault code (LCD: I/P &O/P voltage & frequency, Battery voltage) | |||
| Audible Alarm | Bypass, battery mode, Battery low, Overload, Fault | ||||
| Acoustic Noise | At 1 Meter Distance | <50dB | |||
| Communications | Intelligent RS232 serial port | Software support Windows family software, Linux, Sun network operating system, IBM Aix, Compaq True64 SGI IRIX, FreeBSD, HP-UX and MAC | |||
| SNMP (Optional) | Remote control UPS through SNMP management and Internet | ||||
| USB (Optional) | Windows family software and Mac OS | ||||
| Network Surge Protection | RJ45 I/O port available for network or FAX/Telephone line/Modem | ||||
| Environmental | Operating Temperature | 0~40 ºC | |||
| Operating Humidity | 20-90% (No condensing ) | ||||
| Weight | Net Weight (kgs) | 26.5 | 27 | 10.5 | 11 |
| UPS Dimension | L*W*H (mm) | 455*195*340 | |||