VS1 Indoor Vacuum Breaker
Product Description
VS1 indoor medium voltage Vacuum Circuit Breaker is a three-phase AC 50Hz ,rated voltage 6KV,12KV,24KV switch equipment of power system.
Breaker adopts the integral design of the actuating mechanism and the breaker body, which can be used as a fixed installation unit or as an individual VCB carriage together with handcart. They have a long life expectancy. There is no adverse effect on the vacuum, even from frequent switching of operating and short-circuit currents.
Advantages
VS1 type VCB consist of operating mechanism and arc-extinguish chambers in front-back arrangement, its main conductive circuit is floor model structure. The vacuum arc-extinguish chamber is fixed in a vertical cannular insulation column made of epoxy resin by APG technology, therefore with high anti-creepage function. Such structure design greatly reduces the accumulation of dusts on the surface of vacuum arc- extinguish chamber, it not only can prevent the vacuum extinguish chamber from outside influences, but also can ensure to present high resistance state against the voltage effect even in warm-wet climate or heavy pollution environment.
1 - with reliable interlock functions, suitable for frequent operation
2 - low noise and energy consumed
3 - simple and robust construction.
4 - high operating reliability
5 - mechanical durability of switch : 20000 times, etc
Fields of application
1 - Transformers and distribution substations
2 - Generator control and protection
3 - Capacitor bank control and protection, etc
Mechanical parameters
|
No.
|
Item
|
Unit
|
Date
|
|
1
|
Rated voltage
|
KV
|
12
|
24
|
|
2
|
Clearance between open contacts
|
mm
|
11±1
|
13±1
|
|
3
|
Over travel of moving contact
|
3.5±0.5
|
3.5±0.5
|
|
4
|
Three poles asynchronous time at opening
|
ms
|
≤2
|
≤2
|
|
5
|
Moving contact bounce time at closing
|
ms
|
≤2
|
≤2
|
|
6
|
Average opening speed
|
m/s
|
0.9-1.2
|
0.9-1.2
|
|
7
|
Average closing speed
|
0.6-0.8
|
0.6-0.8
|
|
8
|
Connecting pressure of close contacts
|
N
|
20kA
|
25kA
|
31.5kA
|
40kA
|
20kA
|
25kA
|
31.5kA
|
40kA
|
|
2000
±200
|
2400
±200
|
3100
±200
|
4250
±200
|
2000
±200
|
2400
±200
|
3100
±200
|
4750
±200
|
Main characteristics
|
No.
|
Item
|
Unit
|
|
|
1
|
Rated voltage
|
KV
|
12
|
24
|
|
2
|
Power frequency withstand voltage
|
42
|
65
|
|
3
|
Lightning impulse voltage
(peak value)
|
75
|
125
|
|
4
|
Frequency
|
Hz
|
50
|
50
|
|
5
|
Rated current
|
A
|
630
1250
|
630 1250 1600 2000 2500 3150
|
1250 1600 2000 2500 3150 4000
|
630
1250
|
630 1250 1600 2000
|
1600 200 2500
|
|
6
|
Short circuit breaking current
|
kA
|
20/25
|
31.5
|
40
|
25
|
25/31.5
|
31.5/40
|
|
7
|
Thermal stability current
|
kA
|
20/25
|
31.5
|
40
|
25
|
25/31.5
|
31.540
|
|
8
|
Dynamic stable current
|
kA
|
50/63
|
80
|
100
|
63
|
80
|
100
|
|
9
|
short-circuit making current
|
kA
|
50/63
|
80
|
100
|
63
|
80
|
100
|
|
10
|
Rated current breaking time
|
Times
|
20000
|
20000
|
|
11
|
Short circuit breaking current times
|
Times
|
≤
50
|
≤
30
|
|
12
|
Operation voltage
|
V
|
AC/DC 110/220
|
AC/DC 110/220
|
|
13
|
Input power
|
W
|
70
|
70
|
|
14
|
Storage time
|
s
|
≤
15
|
≤
15
|
|
15
|
3 phase non-synchronous
|
ms
|
≤
2
|
≤
2
|