| Use range | Distribution system and automation system in petrochemical industry,Construction ,power , |
| Case material | Glass fiber reinforced unsaturated polyester |
| Operate mechanism |
Acceleration mechanism with spring energy storage and instantaneous release
Instantaneous on-off double break contact mechanism Front operation, |
| Function |
Rated voltage 660v DC Rated voltage 440v from 100-3150Amp,
Used for infrequent connection and disconnection of circuit and line isolation |
| Conventional thermal current lth A | 63 | 100 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 3150 | ||
| Rated impulse withstand voltage Ui(A) | 750 | 750 | 800 | 1000 | |||||||||
| Dielectric strength(V) | 3 000 | 5000 | |||||||||||
|
Rated Working Current le A |
380V |
AC-21 | 63 | 100 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 3150 |
| AC-22 | 63 | 100 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 3150 | ||
| AC-23 | 50 | 80 | 160 | 250 | 400 | 630 | 800 | 1 00 0 | 1250 | 1250 | 2500 | ||
|
660V |
AC-21 | 50 | 80 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 3150 | |
| AC-22 | 32 | 50 | 160 | 200 | 315 | 400 | 630 | 630 | 800 | 1000 | 1250 | ||
| AC-23 | 25 | 40 | 80 | 125 | 200 | 250 | 250 | 400 | 500 | ||||
| R ated connect capacity A | 10le | ||||||||||||
| Rated break capacity A | 8le | ||||||||||||
| R ated short connect capacity Icm(KA) | 1.7 | 1.7 | 12 | 17 | 30 | 40 | 70 | ||||||
| 1s short impulse current ICW KA | 3 | 3 | 10 | 12 | 20 | 25 | 50 | ||||||
| Operate torque N.M | 3.5 | 3.5 | 6.5 | 10 | 15 | 15 | 27 | 27 | 27 | 60 | 60 | ||