50kVA 40kw Auto Start Silent Dcec Diesel Generator with ATS

Model NO.
BS-C50
Conditions of Use
Land Use
Usage
Common Units, Standby Unit, Emergency Crew
Landuse Type of Unit
Low Noise
Excitation Mode
AC Rotating Exciter
ATS
Optional
Power
40kw/50kVA
Frequency
50Hz
Color
as Per Request
Controller
Smartgen,Deepsea...
Starting Method
Electric Start
Alternator
Stamford
Engine
Dcec 4BTA3.9-G2
Transport Package
Packed in Plywood Cases or Wooden Cases or Foam, E
Specification
As for power
Trademark
BOSSPOWER
Origin
China
HS Code
85021100
Production Capacity
100 Sets / Month
Reference Price
$ 4,860.00 - 6,030.00

Product Description

PRODUCT DESCRIPTION  
 
Frequency: 50HZ;Rotating speed: 1500Rpm
Model Power(KW) Capacity(KVA) Rated current(A) Engine Model Copy Stamford Type
BS- C 25 20 25 36 4B3.9-G1 BS184F
BS- C 40 32 40 57.7 4BT3.9-G2 BS184J
BS- C 70 56 70 101 4BTA3.9-G11 BS224G
BS- C 85 68 85 122.7 6BT5.9-G1 BS224G
BS- C 120 96 120 173.2 6BTA5.9-G2 BS274D
BS- C 140 112 140 202 6BTAA5.9-G2 BS274E
BS- C 160 128 160 230.9 6CTA8.3-G1 BS274F
BS- C 275 220 275 396.9 NTA855-G1A BS314D
BS- C 350 280 350 505 NTA855-G2A BS314E
BS- C 400 320 400 577.4 NTAA855-G7A BS354C
BS- C 450 360 450 649.5 KTA19-G3 BS354C
BS- C 500 400 500 721.7 KTA19-G4 BS354D
BS- C 600 480 600 866 KTAA19-G6 BS354E
BS- C 750 600 750 1082.6 KTA38-G2 BS404B
BS- C 800 640 800 1154.7 KTA38-G2B BS404C
BS- C 900 720 900 1299 KTA38-G2A BS404D
BS- C 800 800 1000 1443.4 KTA38-G5 BS404E
BS- C 1250 1000 1250 1804.3 KTA50-G3 BS404G
           
Frequency: 60HZ;Rotating speed: 1800Rpm
Model Power(KW) Capacity(KVA) Rated current(A) Engine Model Copy Stamford Type
BS- C 29 23 29 41.5 4B3.9-G1 184E
BS- C 43 34 43 61.3 4BT3.9-G1 184H
BS- C 63 50 63 90.2 4BTA3.9-G2 224D
BS- C 80 64 80 115.5 4BTA3.9-G11 224F
BS- C 94 75 94 135.3 6BT5.9-G2 224G
BS- C 125 100 125 180.4 6BTA5.9-G2 274D
BS- C 150 120 150 216.5 6BTAA5.9-G2 274E
BS- C 188 150 188 270.6 6CTA8.3-G2 274F
BS- C 250 200 250 360.9 NT855-GA 274J
BS- C 394 315 394 568.3 NTA855-G3 314E
BS- C 438 350 438 631.5 KTA19-G2 314F
BS- C 513 410 513 739.8 KTA19-G3 354C
BS- C 625 500 625 902 KTAA19-G5 354D
BS- C 688 550 688 992.3 KTAA19-G6A 354E
BS- C 775 620 775 1118.6 KT38-G 354F
BS- C 906 725 906 1308 KT38-G2 404C
BS- C 1000 800 1000 1443.4 KT38-G2A 404D
More specific parameters to choose and we can provide original Stamford generator.
Genset Model: BS- C50
Prime Power (kw/kva) 40/50 Standby Power(kw/kva) 44/55
Voltage (v) 400/230 Rated Speed (rpm) 1500
Frequency (Hz) 50 Rated Current (A) 72
Connection: 3 phase 4 wire Power Factor: 0.8
Engine Model: 4BTA3.9-G2 Alternator Model: BS 224D
Net Weight (kgs)-Open 9 00 Net Weight (kgs)-Silent 1450
Dimensions (mm)-Open 1 950x830x1270 Dimensions (mm)-Silent 2 400x950x1360
Engine Parameter:
Manufacturer/Model:               Aspiration:                              Fuel System:         
Cylinder numbers
Displacement:
Bore x Stroke
Compression Ratio:
Max. Power:
Governing System:
DCEC, 4 BTA3.9-G2 , 4 stroke
Turbocharged,

Direct type fuel pump
4 cylinders in line
3.9 L
102 x 120 mm
16.5
55KW / 75HP
Electronical
Exhaust System
Exhaust Volume:
Exhaust temperature:
Max. Allowed Back Pressure:
 14.8m³/min
497ºC
  10 KPa
Intake System
Max. Allowed Pressure:
Gas Volume:
Air Flow:
6.2 kPa
5.9m³/min
136 m³/min
Fuel System
      100% Load (Prime):
75% Load(Prime):
50% Load (Prime):
214 g/kw.h
214 g/kw.h
221g/kw.h
Lube System
Oil Capacity:
Oil Consumption:
Bottom shell oil capacity:
Oil Pressure at rated speed:
21 L
≤4g/kw.h
9.5 L
350kPa
Cooling system
Coolant Capacity:
Thermostat:
Max. Water Temperature:
24 L
83-95ºC
100ºC
Alternator Parameter:         Basic Information
The alternators meet the standards of:
GB755, BS5000, VDE00530, NEMAMG1-22,IED34-1,CSA22.2 and AS1350
Technical Data:
Manufacturer:
Phases:
Connection:
Bearing numbers:
Power Factor:
Protection Class:
Altitude Condition:
Excitation:
Insulation class/Temp. rise class:
Tel. Influence Factor TIF:
Tel. Harmonic Factor THF:
Steady State Voltage Regulation:
Alternator Capacity:
Efficiency:
Cooling Air Flow:
   Copy Stamford BS 224D
 3
  3 phase 4 wire, Y type
  1
 0.8
 IP23
 ≤1000M
 Brushless, self-excitation
  H / H
  <50
 <2%
 ≤±1%
  40KW
 88. 2%
 0.216m³/s
 
PRODUCT SHOWS  

50kVA 40kw Auto Start Silent Dcec Diesel Generator with ATS


 
PRODUCT ADVANTAGE  
 
(1)The silent canopy we use cold-rolled sheet, all positions are stronger.
 
(2)Our spraying plastics all go through pre-treatment of pickling and phosphating, so that the surface of the
    
    painting will not change color even if placed outside for five years.

 
(3)Canopy color painted by customer's requirement.
 
(4)Strict test including 50% load,75% load,100% load and 110% Load .
 
(5)Forklift mouth in base frame for easy loading and discharging.
 
(6)Logo made by customer's requirement if order quantity ≥10units or a full container.

50kVA 40kw Auto Start Silent Dcec Diesel Generator with ATS
50kVA 40kw Auto Start Silent Dcec Diesel Generator with ATS
FAQ  
Q: Do you offer OEM service?
A: Yes
Q: What is your payment term?
A: 30% T/T in advance, the rest payment before shipment.  Or irrevocable L/C.
Q: What is your lead time?
A: About 30 days after receiving deposit or original L/C.But if your order with some special design, then the
    delivery time is longer.

Q: What certificates do you have?
A: We have CE, ISO. And we can apply for specific certificate for different country such as SONCAP for Nigeria,
     CIQ for Egypt, SASO for Saudi Arabia, etc

Q:What is your MOQ?
A: Above 1pc
Q. Which port do you often use when export?
A: Fuzhou Port, or as customer request.
Q.How to choose the power?
A. : Collect all power of your equipments,take the current into your consideration.
Q.What is the difference between Prime power and Standby power?
A.:Prime power is 12hours continous power,one hour 10% over load in every 12 running hours is allowed.
Standby power is the limit value of maximum output for emergency use. Overloading is prohibited
Q.What about the warranty
Guarantee for one year or 1000 hours (accord to whichever reach first) from ex-factory date.During the guarantee period,
our company will provide the free easy damaged spare part for problems caused by our quality of production or raw material
except the damageable spare parts of diesel engine caused by customer's incorrect man made operation.After expiration,
our company provides cost parts maintenance for gen-set.

 
CONTACT US   

 

 