Sp3u-48200 AC Input System

Model NO.
SP3U-48200
Brand
DSS
Output Voltage
42~ 58VDC
Standard Battery MCB
125ax2
Input MCB
125A/ 2px1
Power Supply Mode
Single Phase (3 Phase Is Optional)
Transport Package
Export Carton
Specification
CE
Trademark
SOROTEC
Origin
China Mainland
HS Code
85044020
Production Capacity
500PCS/Month
Reference Price
Please contact us for quote

Product Description

SP3U-48200 AC Input System

 

Key Features:

  1. Constructed with standard 19 inch screen, which has the advantage of wide use.
  2. The data center area and the installation cost can be saved due to its mall size and the embedded installation.
  3. Wide input voltage range (85 -290Vac), the power gird is adaptable.
  4. Perfect lightning protection.
  5. Rectifiers are hot pluggable. Easy and quick on line maintenance.
  6. The rectifier uses DSP(Digital Signaling Processor) ology, makes the power density ran up to 14W/In3.
  7. Battery management, prolongs the life of the battery well.
  8. Have passed CE,UL,TLC, and other related certifications.
  9. Excellent energy conservation and environmental protection.

Technical Specifications of SP3U-48200 AC Input System :

SP3U-48200
AC Distribution
Power supply mode : Single phase (3 phase is optional)
Input Voltage: 80 ~ 300 Vac
Input MCB: 125A/ 2P×1
DC Distribution
Output Voltage 42~ 58Vdc
Standard Battery MCB 125A×2
Standard LLVD Output Route 63A× 2,  32A× 4,  16A× 2
Rectifier
Mode SR4850 SR4850 Plus
Input
Input Voltage 85Vac ~ 290Vac 85Vac ~ 305Vac
Power Factor 0.99 0.99
Efficiency 92% 96.3% peak
Max. Input Current 18A 22.5A
Output Voltage -42Vdc ~ -58Vdc -42Vdc ~ -58Vdc
Output Current 60A  73A
Operation Temperature -40~+60°C -40~+75°C
Controller STM
Display LCD
CommunicationInterface RS232,Ethernet
Analog input 1batterycurrents, 1busvoltage, 1battery Voltage,2temperatures, 4 midpoint battery voltage
Digitalinputs 2 load fuses, 4 battery fuses, 1 bi - stable contactor statues, 4 user inputs(Optional, need extra board) load fuse and battery fuse can be configured as midpoint battery voltage, load fuse and battery fuse 
Outputs 1 LVD mono or bistable contactors, 1 LVD mono contactor, 8 user relay outputs (Optional, need extra board)
Protocol
Sp3u-48200 AC Input System
Sp3u-48200 AC Input System

 

 